Back |
|
|
Select
refrigerant type : 1.
Ammonia 2.
Freon-22 |
|
|
1.
Capacity Rating of Single Stage Compressor( Refrigerant type
: Ammonia) |
|
|
|
Comp
Model |
Evaporating
Temp in 0C |
Condensing
Temperature |
|
200C |
300C |
400C |
|
Q0 |
Pe |
Q0 |
Pe |
Q0 |
Pe |
|
MX200 |
5 |
270200 |
30.8 |
252600 |
40.9 |
233800 |
51.8 |
|
0 |
222500 |
31.0 |
206800 |
40.3 |
152500 |
49.8 |
|
-10 |
146500 |
30.1 |
133800 |
37.1 |
119900 |
43.3 |
|
-20 |
90400 |
27.1 |
79900 |
31.0 |
- |
- |
|
MX300 |
5 |
405400 |
45.2 |
379000 |
60.4 |
350700 |
76.7 |
|
0 |
333800 |
45.5 |
310300 |
59.4 |
2844900 |
73.8 |
|
-10 |
219800 |
49.5 |
200700 |
54.7 |
179900 |
63.9 |
|
-20 |
135600 |
45.5 |
119800 |
45.5 |
- |
- |
|
MX400 |
5 |
540500 |
59.6 |
505300 |
79.8 |
467600 |
101.6 |
|
0 |
445100 |
60.0 |
413700 |
78.6 |
379900 |
97.7 |
|
-10 |
293000 |
58.2 |
267600 |
72.3 |
239800 |
|
|
-20 |
180900 |
52.2 |
159800 |
60.0 |
- |
- |
|
MX600 |
5 |
810800 |
88.3 |
758000 |
118.6 |
701500 |
151.3 |
|
0 |
667700 |
88.9 |
620600 |
116.7 |
569900 |
145.4 |
|
-10 |
439600 |
86.2 |
401400 |
117.1 |
359800 |
125.8 |
|
-20 |
271300 |
83.6 |
239700 |
88.9 |
- |
- |
|
MX900 |
5 |
1216200 |
131.4 |
1137000 |
176.9 |
1052300 |
226.0 |
|
0 |
1001600 |
132.3 |
930900 |
174.1 |
854800 |
217.1 |
|
-10 |
659400 |
128.3 |
602100 |
160.0 |
539700 |
187.6 |
|
-20 |
407000 |
114.8 |
359600 |
132.3 |
- |
- |
|
| |
Notes:
- Q0= Refrigeration Effect
(Cooling Capacity) in kcal/hr
- Pe= Power required at
compressor shaft in kW
- Capacity is at 1000 rpm
- Power consumption and capacities
are proportional to speed
- Capacity is at 50C
useful superheat for R-22
- Capacity is at 50C
nonuseful superheat gained in suction line for NH3
- Interpolation of ratings is
permissible
- For any condition outside the range
given above please refer to us
|
|
|
|
|
2. Capacity Rating of
Single Stage Compressor (Refrigerant type : Freon-22) |
|
|
|
Comp
Model |
Evaporating
Temp in 0C |
Condensing Temperature |
|
200C |
300C |
400C |
|
Q0 |
Pe |
Q0 |
Pe |
Q0 |
Pe |
|
MX200 |
5 |
247900 |
39.2 |
226500 |
46.9 |
204300 |
59.7 |
|
0 |
207900 |
37.6 |
189000 |
44.9 |
169500 |
52.7 |
|
-10 |
142200 |
34.3 |
127000 |
40.5 |
112500 |
46.6 |
|
-20 |
92800 |
30.6 |
81600 |
35.2 |
69900 |
38.7 |
|
MX300 |
5 |
371900 |
57.8 |
339700 |
69.3 |
306400 |
82.0 |
|
0 |
311800 |
55.4 |
283500 |
66.3 |
254200 |
78.0 |
|
-10 |
213300 |
50.5 |
191500 |
59.8 |
168800 |
69.0 |
|
-20 |
139200 |
45.0 |
122400 |
51.7 |
104900 |
57.1 |
|
MX400 |
5 |
495900 |
76.4 |
453000 |
91.7 |
408600 |
108.6 |
|
0 |
415800 |
73.2 |
378000 |
87.7 |
339000 |
103.4 |
|
-10 |
284400 |
66.7 |
255300 |
79.0 |
225100 |
91.3 |
|
-20 |
185700 |
59.3 |
163200 |
68.3 |
139900 |
75.4 |
|
MX600 |
5 |
723900 |
113.5 |
679500 |
136.5 |
612900 |
161.8 |
|
0 |
623700 |
108.7 |
667100 |
130.5 |
508500 |
154.0 |
|
-10 |
426700 |
98.9 |
363000 |
117.4 |
337700 |
124.9 |
|
-20 |
278500 |
87.8 |
244800 |
101.4 |
209900 |
112.1 |
|
MX900 |
5 |
115900 |
169.1 |
19300 |
203.7 |
919400 |
241.7 |
|
0 |
935600 |
162.0 |
850700 |
194.7 |
762800 |
229.9 |
|
-10 |
640000 |
147.3 |
574500 |
175.1 |
506600 |
202.7 |
|
-20 |
2417800 |
130.7 |
367200 |
151.0 |
314900 |
167.1 |
|
|
Notes:
- Q0= Refrigeration Effect (Cooling
Capacity) in kcal/hr
- Pe= Power required at compressor shaft
in kW
- Capacity is at 1000 rpm
- Power consumption and capacities are proportional
to speed
- Capacity is at 50C useful superheat for
R-22
- Capacity is at 50C nonuseful superheat
gained in suction line for NH3
- Interpolation of ratings is permissible
- For any condition outside the range given above
please refer to us
|
|
|
|
|
|
|
|